<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>
<channel>
	<title>Michael Smith Switch Gear</title>
	<atom:link href="http://www.michaelsmithswitchgear.co.uk/feed/" rel="self" type="application/rss+xml" />
	<link>http://www.michaelsmithswitchgear.co.uk</link>
	<description>Just another WordPress weblog</description>
	<lastBuildDate>Wed, 19 May 2010 14:50:21 +0000</lastBuildDate>
	<generator>http://wordpress.org/?v=2.8.6</generator>
	<language>en</language>
	<sy:updatePeriod>hourly</sy:updatePeriod>
	<sy:updateFrequency>1</sy:updateFrequency>
			<item>
		<title>Retrofit Schneider Merlin Gerin Marterpact M to NW ACB</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/retrofit-schneider-merlin-gerin-marterpact-m-to-nw-acb/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/retrofit-schneider-merlin-gerin-marterpact-m-to-nw-acb/#comments</comments>
		<pubDate>Fri, 16 Apr 2010 11:00:38 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=323</guid>
		<description><![CDATA[At Michael Smith Switchgear we understand the importance and implications of loosing power and having readily available spares for LV Switchgear, ACBs and MCCBs for a disastor situation.
Over the years ee have been developing a quick solution to retrofit Schneider Merlin Gerin ACBs from Masterpact M to Masterpact NW through the entire range of sizes from 800A [...]]]></description>
			<content:encoded><![CDATA[<p>At Michael Smith Switchgear we understand the importance and implications of loosing power and having readily available spares for LV Switchgear, ACBs and MCCBs for a disastor situation.</p>
<p>Over the years ee have been developing a quick solution to retrofit Schneider Merlin Gerin ACBs from Masterpact M to Masterpact NW through the entire range of sizes from 800A to 6300A. </p>
<p>The procedure requires a small shutdown and then at the end of the shut down the old Merlin Gerin Masterpact M ACB is removed and the new Merlin Gerin Masterpact NW ACB is installed, along with the new chassis, intergrated control (if applicable), and readily available spares.</p>
<p>Michael Smith Switchgear retrofit any ACB and can replace any manufactures ACBs with new ACBs.  The works will be arranged at a time to suit the business needs and with minimal disruption.</p>
<p> </p>
<p>If you have any queries please do not hesitate to <a href="http://www.michaelsmithswitchgear.co.uk/contact-us/" target="_blank">contact us</a>.</p>

<div class="ngg-galleryoverview" id="ngg-gallery-4-323">


	
	<!-- Thumbnails -->
		
	<div id="ngg-image-17" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/retrofit/15122008048-medium.jpg" title="Masterpact M50 4 pole" rel="lightbox[retrofit]">
				<img title="Masterpact M50 4 pole" alt="Masterpact M50 4 pole" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/retrofit/thumbs/thumbs_15122008048-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-18" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/retrofit/img_0678-medium.jpg" title="Installation of New Merlin Gerin Masterpact NW ACB" rel="lightbox[retrofit]">
				<img title="Installation of New Merlin Gerin Masterpact NW ACB" alt="Installation of New Merlin Gerin Masterpact NW ACB" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/retrofit/thumbs/thumbs_img_0678-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-19" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/retrofit/website-pictures-3.jpg" title="Terasaki ACBs Fitted and control Integrated" rel="lightbox[retrofit]">
				<img title="Terasaki ACBs Fitted and control Integrated" alt="Terasaki ACBs Fitted and control Integrated" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/retrofit/thumbs/thumbs_website-pictures-3.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 	 	
	<!-- Pagination -->
 	<div class='ngg-clear'></div>
 	
</div>


]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/retrofit-schneider-merlin-gerin-marterpact-m-to-nw-acb/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Schneider Merlin Gerin Masterpact M ACB and Spares</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/schneider-merlin-gerin-masterpact-m-acb-and-spares/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/schneider-merlin-gerin-masterpact-m-acb-and-spares/#comments</comments>
		<pubDate>Wed, 11 Nov 2009 11:25:16 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=191</guid>
		<description><![CDATA[Michael Smith Switchgear are fully aware of the concerns of customers with obsolete equipment on site.  We now have a full range of Obsolete Merlin Gerin Masterpact M ACBs to meet your site specific needs.  These have been serviced and are ready for installation or are perfect as spares.
Michael Smith Switchgear can also replace any existing ACBs [...]]]></description>
			<content:encoded><![CDATA[<p>Michael Smith Switchgear are fully aware of the concerns of customers with obsolete equipment on site.  We now have a full range of Obsolete Merlin Gerin Masterpact M ACBs to meet your site specific needs.  These have been serviced and are ready for installation or are perfect as spares.</p>
<p>Michael Smith Switchgear can also replace any existing ACBs and retrofit new ACBs into the same space.</p>
<p> </p>
<p>Please do not hesitate to <a href="http://www.michaelsmithswitchgear.co.uk/?page_id=12" target="_self">contact us</a> for more information.</p>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/schneider-merlin-gerin-masterpact-m-acb-and-spares/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Power Factor Correction &#8211; PFC</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/power-factor-correction-pfc/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/power-factor-correction-pfc/#comments</comments>
		<pubDate>Thu, 01 Oct 2009 11:00:23 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=199</guid>
		<description><![CDATA[Michael Smith Switchgear manufacture bespoke Power Factor Correction (PFC) cubicles.  These can be manufactured as a standalone unit or can be incorporated into a LV Switchgear Panel.
Power Factor Correction (PFC) will help to reduce the reactive power consumed within a business and therefore save money.  A Power Quality Survey can be arranged to calculate the requirement [...]]]></description>
			<content:encoded><![CDATA[<p>Michael Smith Switchgear manufacture bespoke Power Factor Correction (PFC) cubicles.  These can be manufactured as a standalone unit or can be incorporated into a LV Switchgear Panel.</p>
<p>Power Factor Correction (PFC) will help to reduce the reactive power consumed within a business and therefore save money.  A Power Quality Survey can be arranged to calculate the requirement of Power Factor Correction (PFC) equipment within an existing system.</p>
<p>If you have any queries please <a href="http://www.michaelsmithswitchgear.co.uk/?page_id=12" target="_blank">contact us</a>.</p>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/power-factor-correction-pfc/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Electrical Control Panels</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/electrical-control-panels/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/electrical-control-panels/#comments</comments>
		<pubDate>Sat, 01 Aug 2009 11:00:08 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=195</guid>
		<description><![CDATA[Michael Smith Switchgear deisgn and manufacture a full range of Electrical control panels including Automatic Changeover Panels, Static Transfer Switches, Lighting Control Panels, Motor Control Centres, Pump Control Panels, HVAC Panels and many more.
These can incorporate DOL Starters, Star-Delta Starters and Variable Speed Drives (VSD) to suit your requirements.
]]></description>
			<content:encoded><![CDATA[<p>Michael Smith Switchgear deisgn and manufacture a full range of Electrical control panels including Automatic Changeover Panels, Static Transfer Switches, Lighting Control Panels, Motor Control Centres, Pump Control Panels, HVAC Panels and many more.</p>
<p>These can incorporate DOL Starters, Star-Delta Starters and Variable Speed Drives (VSD) to suit your requirements.</p>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/electrical-control-panels/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>LV Switchgear Basic Functions</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/lv-switchgear-basic-functions/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/lv-switchgear-basic-functions/#comments</comments>
		<pubDate>Fri, 31 Jul 2009 12:00:50 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=143</guid>
		<description><![CDATA[LV Switchgear
The basic functions of LV Switchgear
The role of lv switchgear is:
1. Electrical protection
2. Safe isolation from live parts
3. Local or remote switching
National and international standards define the manner in which electric circuits of LV installations must be realized, and the capabilities and limitations of the various switching devices which are collectively referred to as [...]]]></description>
			<content:encoded><![CDATA[<h1>LV Switchgear</h1>
<h1>The basic functions of LV Switchgear</h1>
<h4>The role of lv switchgear is:<br />
1. Electrical protection<br />
2. Safe isolation from live parts<br />
3. Local or remote switching</h4>
<p>National and international standards define the manner in which electric circuits of LV installations must be realized, and the capabilities and limitations of the various switching devices which are collectively referred to as lv switchgear.</p>
<p>The main functions of lv switchgear are:</p>
<ul class="bullet1">
<li>Electrical protection</li>
<li>Electrical isolation of sections of an installation</li>
<li>Local or remote switching</li>
</ul>
<p>Electrical protection at low voltage is (apart from fuses) normally incorporated in circuit-breakers, in the form of thermal-magnetic devices and/or residual-current operated tripping devices (less-commonly, residual voltage- operated devices &#8211; acceptable to, but not recommended by IEC).</p>
<p>In addition to those functions above, other functions, namely:</p>
<ul class="bullet1">
<li>Over-voltage protection</li>
<li>Under-voltage protection</li>
</ul>
<p>are provided by specific devices (lightning and various other types of voltage-surge arrester, relays associated with contactors, remotely controlled circuit-breakers, and with combined circuit-breaker/isolators… etc)</p>
<p><span style="color: #ffffff;">LV Switchgear LV Switchgear  LV Switchgear  LV Switchgear  LV Switchgear  LV Switchgear LV Switchgear LV Switchgear LV Switchgear LV Switchgear LV Switchgear LV Switchgear LV Switchgear LV Switchgear LV Switchgear</span></p>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/lv-switchgear-basic-functions/feed/</wfw:commentRss>
		<slash:comments>1</slash:comments>
		</item>
		<item>
		<title>Package Substation</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/package-substation/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/package-substation/#comments</comments>
		<pubDate>Mon, 20 Apr 2009 07:00:48 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=139</guid>
		<description><![CDATA[Package Substations are becoming more popular within the marketplace as a space reducing option. They offer an all-in-one solution to the customer for the HV Switch, Transformer &#38; LV Switchgear.  All within one finished product.
Michael Smith Switchgear Ltd offers a complete service for the manufacture and assembly of indoor package substations tailored to meet your [...]]]></description>
			<content:encoded><![CDATA[<p>Package Substations are becoming more popular within the marketplace as a space reducing option. They offer an all-in-one solution to the customer for the HV Switch, Transformer &amp; LV Switchgear.  All within one finished product.</p>
<p>Michael Smith Switchgear Ltd offers a complete service for the manufacture and assembly of indoor package substations tailored to meet your specific needs.</p>
<p> </p>

<div class="ngg-galleryoverview" id="ngg-gallery-3-139">


	
	<!-- Thumbnails -->
		
	<div id="ngg-image-10" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/img_0804-medium.jpg" title="800KVA Transformer Complete with Close Coupled SF6 HV Switch and LV Switchgear" rel="lightbox[package-substation]">
				<img title="img_0804-medium.jpg" alt="img_0804-medium.jpg" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/thumbs/thumbs_img_0804-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-11" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/img_0805-medium.jpg" title=" " rel="lightbox[package-substation]">
				<img title="img_0805-medium.jpg" alt="img_0805-medium.jpg" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/thumbs/thumbs_img_0805-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-12" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/img_0813-medium.jpg" title=" " rel="lightbox[package-substation]">
				<img title="img_0813-medium.jpg" alt="img_0813-medium.jpg" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/thumbs/thumbs_img_0813-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-13" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/img_0818-medium.jpg" title=" " rel="lightbox[package-substation]">
				<img title="img_0818-medium.jpg" alt="img_0818-medium.jpg" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/thumbs/thumbs_img_0818-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-15" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/img_0806-medium.jpg" title=" " rel="lightbox[package-substation]">
				<img title="img_0806-medium.jpg" alt="img_0806-medium.jpg" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/thumbs/thumbs_img_0806-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 		
	<div id="ngg-image-16" class="ngg-gallery-thumbnail-box"  >
		<div class="ngg-gallery-thumbnail" >
			<a href="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/img_0816-medium.jpg" title=" " rel="lightbox[package-substation]">
				<img title="img_0816-medium.jpg" alt="img_0816-medium.jpg" src="http://www.michaelsmithswitchgear.co.uk/wordpress/wp-content/gallery/package-substation/thumbs/thumbs_img_0816-medium.jpg" width="100" height="100" />
			</a>
		</div>
	</div>
	 	 	
	<!-- Pagination -->
 	<div class='ngg-clear'></div>
 	
</div>


]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/package-substation/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Schneider&#8217;s Merlin Gerin NSX Range MCCB</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/schneiders-merlin-gerin-nsx-range-mccb/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/schneiders-merlin-gerin-nsx-range-mccb/#comments</comments>
		<pubDate>Mon, 02 Mar 2009 07:00:15 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=131</guid>
		<description><![CDATA[Schneider&#8217;s Merlin Gerin NSX Range of MCCB Released
Schneider released their new range of MCCBs (The NSX Range) in November 2008, and sine then Michael Smith Switchgear have used these as a standard.  These MCCBs fit within the same physical space as their previous model (The NS range) with the option available to add numerous more [...]]]></description>
			<content:encoded><![CDATA[<p>Schneider&#8217;s Merlin Gerin NSX Range of MCCB Released</p>
<p>Schneider released their new range of MCCBs (The NSX Range) in November 2008, and sine then Michael Smith Switchgear have used these as a standard.  These MCCBs fit within the same physical space as their previous model (The NS range) with the option available to add numerous more amounts of accessories.</p>
<p>Other Materials are still being used to customer requirements.<br />
Our <a href="http://www.michaelsmithswitchgear.co.uk/?page_id=8">Components List</a> is by no means a definative list.</p>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelsmithswitchgear.co.uk/switchgear/schneiders-merlin-gerin-nsx-range-mccb/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Low Voltage Switchgear &#8211; LV Switchgear New Website</title>
		<link>http://www.michaelsmithswitchgear.co.uk/switchgear/lv-switchgear-website-new-launch/</link>
		<comments>http://www.michaelsmithswitchgear.co.uk/switchgear/lv-switchgear-website-new-launch/#comments</comments>
		<pubDate>Mon, 05 Jan 2009 07:00:04 +0000</pubDate>
		<dc:creator>sean</dc:creator>
				<category><![CDATA[Switchgear]]></category>

		<guid isPermaLink="false">http://www.michaelsmithswitchgear.co.uk/?p=126</guid>
		<description><![CDATA[Low Voltage Switchgear &#8211; LV Switchgear New Website
Welcome to the new look Michael Smith Switchgear website.
Michael Smith Switchgear are a leading manufacturer of LV Switchgear, specialising in Schneider, Merlin Gerin, ABB, Terasaki &#38; Dorman Smith products.
Michael Smith Switchgear have been manufacturing LV Switchgear for 25 years and are well established within the marketplace.
Read More about us.
]]></description>
			<content:encoded><![CDATA[<p>Low Voltage Switchgear &#8211; LV Switchgear New Website</p>
<p>Welcome to the new look Michael Smith Switchgear website.</p>
<p>Michael Smith Switchgear are a leading manufacturer of LV Switchgear, specialising in Schneider, Merlin Gerin, ABB, Terasaki &amp; Dorman Smith products.</p>
<p>Michael Smith Switchgear have been manufacturing LV Switchgear for 25 years and are well established within the marketplace.</p>
<p>Read More <a href="http://www.michaelsmithswitchgear.co.uk/">about us</a>.</p>